Key Product Data
Manufacturer: Allen-Bradley / Rockwell Automation
Catalog Number: 194R-J30-1753
Product Family: Bulletin 194R
Product Type: Fused Disconnect Switch
UPC: 781180651021
Fuse Class: UL Class J / CSA HRCI-J
Rated Current: 30 A
Number of Poles: 3
Switching Function: OFF-ON
Construction: Open type
Fuse Status Indication: Not included in this catalog configuration
Lifecycle Status: Active
A Fused Disconnect for Three-Phase Power Circuits
The Allen-Bradley 194R-J30-1753 is a three-pole fused disconnect switch designed for industrial power distribution and equipment isolation. It belongs to the Bulletin 194R range of fused and non-fused rotary disconnect switches.
This model is configured for UL Class J and CSA HRCI-J fuses, with a 30 A switch rating. The fused arrangement combines a manual disconnecting function with fuse-based overcurrent and short-circuit protection when correctly equipped with compatible fuse links.
Its open construction is intended for installation within an appropriate electrical enclosure or panel assembly. Unlike a complete enclosed disconnect, the switch itself does not provide a standalone environmental enclosure or external operating handle.

Understanding the J30-1753 Configuration
The catalog number identifies several important characteristics of the device:
| Code Element | Meaning |
|---|---|
| 194R | Bulletin 194R fused and non-fused disconnect switch family |
| J | UL Class J / CSA HRCI-J fuse type |
| 30 | 30 A rating |
| 1753 | Three-pole switch |
| No additional S suffix | No fuse-status indication specified in this catalog number |
The J designation is particularly important when selecting replacement fuses. A fuse with the same current rating but a different class is not automatically compatible. The fuse class, physical dimensions, voltage rating and interrupting characteristics must all match the switch and the electrical installation.
Electrical Ratings and Fuse Selection
The 194R-J30-1753 is a 30 A fused disconnect. Rockwell Automation's Bulletin 194R selection guide lists the J30 version for three-phase applications and provides motor horsepower references at common North American supply voltages.
| Three-Phase Supply Voltage | Published Maximum Motor Rating |
|---|---|
| 240 V AC | 7.5 HP |
| 480 V AC | 15 HP |
| 600 V AC | 20 HP |
These horsepower figures are selection references, not a substitute for checking the motor's full-load current, starting characteristics, fuse selection and applicable electrical codes.
The fuse links must be selected separately according to the protected circuit. The disconnect switch's 30 A rating should not be interpreted as a universal instruction to install 30 A fuses in every application.
Can't find the version you need?
Open Construction: Panel and Enclosure Installation
The 194R-J30-1753 is supplied as an open disconnect switch. Its switch body is listed with IP20 protection, so it should be installed within a suitable electrical enclosure or panel assembly.
The complete operating arrangement also requires attention to the handle and shaft. Rockwell Automation's selection guide specifies that an order for a complete installation must account for the disconnect switch, operating shaft, handle and any required accessories.
This is important when replacing an existing unit: the switch body alone may not provide the same door-coupled operating arrangement as the original assembly.
Applications in Industrial Power Systems
The 194R-J30-1753 is intended for applications where a three-pole fused disconnect is needed to switch and protect a suitable three-phase circuit.
Common installation scenarios include:
- Machinery incoming power: Used as a fused disconnecting point for the incoming supply to industrial machinery.
- Motor branch circuits: Applied in suitable motor circuits where the motor load and fuse coordination match the switch's ratings.
- Control panel power distribution: Installed as a disconnecting and fuse-protection point for a dedicated equipment power branch.
- Industrial equipment isolation: Provides a manual OFF-ON switching point that can be incorporated into an equipment isolation arrangement.
- Electrical cabinet assemblies: Used in panel designs where an open switch body is mounted inside a separate enclosure and operated through a compatible handle and shaft.
For motor circuits, the switch and fuse combination must be coordinated with the motor's starting current and the required protection characteristics. The disconnect itself does not replace a motor overload relay or other required motor protection.

Components to Check When Ordering
A replacement for an installed 194R-J30-1753 may require more than the switch body. Check the following components against the existing assembly:
| Component | What to Verify |
|---|---|
| Disconnect switch | 194R-J30-1753, 30 A, three-pole, Class J |
| Fuse links | Compatible UL Class J / CSA HRCI-J type and appropriate circuit rating |
| Operating shaft | Correct length and connection for the panel arrangement |
| Operating handle | Compatible handle type, mounting and required enclosure rating |
| Auxiliary contacts | Required contact arrangement and compatibility |
| Terminal protection | Whether terminal covers or other accessories are needed |
The handle and shaft are separately selected components in the Bulletin 194R system. Do not assume they are included with this open switch catalog number.
Related 194R Catalog Numbers
The following models share the 194R-J30-1753 base configuration but have different handle, shaft or accessory arrangements. They are separate catalog numbers, not alternative UPCs for the base switch.
| Catalog Number | Configuration |
|---|---|
| 194R-J30-1753 | Open, 30 A, three-pole, Class J fused disconnect switch |
| 194R-J30-1753-PBS1 | Kit with standard black handle and S1 shaft |
| 194R-J30-1753-PYS1 | Kit with standard red/yellow handle and S1 shaft |
| 194R-J30-1753-PBN1 | Kit with standard black handle, NFPA 79 arrangement and R1 shaft |
| 194R-J30-1753-PYN1 | Kit with standard red/yellow handle, NFPA 79 arrangement and R1 shaft |
The kitted versions include specific operating components. Their handle style, shaft length and enclosure compatibility should be checked before selecting one as a replacement.
Frequently Asked Questions
Is the 194R-J30-1753 a fused or non-fused disconnect?
It is a fused disconnect configured for UL Class J / CSA HRCI-J fuse links.
How many poles does this switch have?
It is a three-pole disconnect switch for suitable three-phase circuits.
Does the 194R-J30-1753 include a handle and shaft?
The base catalog number identifies the open switch. The operating handle and shaft are separately selected components in the Bulletin 194R system.
Does this model provide fuse-status indication?
The base catalog number does not include the additional S suffix used to identify fuse-status indication on applicable 194R models.
Can it be installed without an enclosure?
The switch body is an open-type IP20 device. It should be installed within a suitable electrical enclosure or panel assembly.
Can a non-Class J fuse be used as a substitute?
Do not assume so. The switch is specifically configured for UL Class J / CSA HRCI-J fuse links. Confirm the fuse class, dimensions, voltage and protective characteristics before replacement.