Key Product Data
Brand: Allen-Bradley
Model: 280E-FN-25-C
Product Family: ArmorStart Bulletin 280E
Product Type: Distributed Motor Starter Base Module
UPC: 885630116389
Communication: EtherNet/IP
Enclosure Rating: IP67 / NEMA Type 4
Motor Supply Voltage: 200–575V AC, three-phase
Control Voltage: 24V DC
Motor Current Range: 3.2–16 A
Short-Circuit Protection Device Rating: 25 A
Connection Type: Conduit entrance
Network Ports: Two D-coded, 4-pin female M12 Ethernet connectors
Digital Inputs: 4
Digital Outputs: 2
Approximate Shipping Weight: 10.4 kg
Important rating distinction: the "25" in the catalog number identifies the short-circuit protection device rating. It does not mean the motor starter has a 25 A operating-current range. The published motor current range for this configuration is 3.2–16 A.
Product Overview
The Allen-Bradley 280E-FN-25-C is an ArmorStart distributed motor starter base module designed for motor control in industrial environments where control equipment is installed close to the driven machinery. It combines motor-starter functionality with EtherNet/IP communication, allowing the unit to exchange operating data and control signals with a networked automation system.
Its IP67 enclosure supports installation in areas exposed to dust and water, while the conduit-entry configuration provides a conventional wiring approach for power and control connections. The module is intended for distributed motor-control arrangements that reduce the need to route every motor circuit back to a centralized control cabinet.
This catalog number is identified as a base-module-only configuration. It should therefore be distinguished from a complete, separately configured ArmorStart assembly. Confirm the installed module configuration and required accessories before selecting it as a replacement.

Electrical and Network Capabilities
The 280E-FN-25-C is designed for three-phase motor applications with a supply voltage range of 200–575V AC. Its published motor current range is 3.2–16 A, with a 25 A rated short-circuit protection device.
EtherNet/IP communication is provided through an embedded two-port Ethernet switch. The two D-coded M12 female connectors support network connections, including Device Level Ring (DLR) network arrangements. The module also provides four digital inputs and two digital outputs for local control and status-related functions.
An embedded web server provides access to status, diagnostics and configuration functions. These features help integrate the distributed starter into a plant-wide control network and make operating information available for maintenance and troubleshooting.
Installation and Environmental Characteristics
The 280E-FN-25-C uses an IP67 enclosure and is also identified with a NEMA Type 4 rating. This enclosure design is intended for industrial installation where protection against dust and water exposure is important.
The conduit-entry version is different from the ArmorConnect power-media version. The final "C" in the catalog number identifies the conduit connection arrangement; the corresponding "R" variant uses ArmorConnect power media. These configurations should not be treated as interchangeable without checking the existing wiring and installation requirements.
Other relevant installation characteristics include:
- Three-pole power circuit
- 600V power-circuit insulation rating
- 6kV rated impulse voltage
- 50/60Hz operating frequency
- Power and ground terminal wire strip length: 9 mm
- Power and ground terminal tightening torque: refer to the applicable installation instructions
Can't find the version you need?
Where the 280E-FN-25-C Fits
This ArmorStart module is suited to distributed motor-control installations where individual motor starters are positioned near conveyors, processing equipment, production machinery or other motor-driven loads.
Typical application contexts include:
- Conveyor and material-handling systems
- Distributed motor-control stations
- Packaging and production machinery
- Industrial equipment using EtherNet/IP-based control networks
- Motor-control installations requiring IP67-rated enclosures
The module's network interface and local I/O make it suitable for installations where motor status and control signals need to be exchanged with a central PLC or other EtherNet/IP-enabled automation equipment.
Model Selection: Check These Differences
The 280E-FN-25-C belongs to a family of ArmorStart base-module configurations. Several catalog-number details are important when identifying the correct unit.
|
Catalog number |
Main distinction |
|---|---|
|
280E-FN-25-C |
25 A rated short-circuit protection device; conduit entrance |
|
280E-FN-25-R |
Same 25 A device rating; ArmorConnect power-media connection |
|
280E-FN-10-C |
10 A rated short-circuit protection device; conduit entrance |
|
280E-FN-10-R |
10 A rated short-circuit protection device; ArmorConnect power-media connection |
The 10 and 25 designations refer to the short-circuit protection device rating, not the motor's full-load current. The connection suffix also matters: a conduit-entry model and an ArmorConnect model have different connection arrangements.

Important Checks Before Replacement
When replacing an existing ArmorStart unit, verify more than the model-family name:
- Catalog number: Confirm the complete 280E-FN-25-C designation, including the connection suffix.
- Motor rating: Check the motor's full-load current against the module's 3.2–16 A range.
- Supply voltage: Confirm the three-phase supply falls within the 200–575V AC range.
- Network connection: Verify that the existing installation uses EtherNet/IP and the appropriate M12 connections.
- Wiring arrangement: Confirm that the equipment uses conduit entry rather than ArmorConnect power media.
- Module configuration: Check the existing assembly and its associated components before assuming a base module alone will restore the complete motor-starter function.
Frequently Asked Questions
Is the 280E-FN-25-C a complete motor starter?
Rockwell identifies this catalog number as a base-module-only configuration. It should not automatically be treated as a complete, independently configured motor-starter assembly. Check the original equipment configuration and installation documentation before ordering.
Does 25 A mean the motor can operate at 25 A?
No. The 25 A designation refers to the rated short-circuit protection device. The published motor current range for this model is 3.2–16 A.
What communication protocol does this module use?
It uses EtherNet/IP and has two D-coded, 4-pin female M12 Ethernet connectors. The embedded switch supports network configurations that include Device Level Ring.
What is the difference between 280E-FN-25-C and 280E-FN-25-R?
The principal difference is the power connection arrangement. The "C" version uses conduit entry, while the "R" version uses ArmorConnect power media. Check the existing installation before selecting either version.
Can the 280E-FN-25-C be installed in a wet or dusty industrial environment?
Its IP67 and NEMA Type 4 enclosure ratings make it suitable for installations requiring protection against dust and water exposure. Actual suitability still depends on installation conditions, cable entries and correct sealing.
What should be checked when sourcing a replacement?
Confirm the full catalog number, motor current range, supply voltage, communication protocol, connection type and the configuration of the existing ArmorStart assembly. Matching only the 25 A designation is not sufficient.
Hot Tags: 280e-fn-25-c allen-bradley armorstart distributed motor starter base module, China 280e-fn-25-c allen-bradley armorstart distributed motor starter base module suppliers, magnetic motor protector, magnetic motor starter, manual motor protector, motor control assembly, motor controller, motor electronic protection relay